3 |
Distribusi DC |
Tegangan output sistem |
Dirating output:125VDC |
Range sing bisa diatur: 90VDC-150VDC terus-terusan luwes |
Sistem output saiki |
125V/20A |
Regulasi beban sistem |
≤±0,5% |
Regulasi voltase sistem |
≤±0,5% |
Presisi stabilitas sistem |
≤±0,5% |
Kapabilitas enggo bareng saiki |
enggo bareng modul saiki ora luwih saka ± 5% |
Swara bobot imbangan telpon |
≤2mV(@230Vac,beban penuh) |
Tegangan swara puncak-puncak |
≤200mV(0 MHz ~ 20 MHz) (@220Vac,setengah beban ~ beban penuh) |
nilai watesan saiki sistem |
Sistem daya: 1-22A,Cathetan: bisa diatur terus-terusan |
Sistem drop voltase |
Ing beban lengkap. gulung voltase saka distribusi DC ing rak bakal ngisor 500 mV |
Distribusi output |
Distribusi beban:3@ 135A Terminal Rel Gunung |
Distribusi baterei |
Distribusi baterei:1*@135A Terminal rel gunung |
4 |
Modul lan Unit Monitoring |
Rectifier hot-swap |
Hot-swap kasedhiya.ora mengaruhi operasi sistem |
Indikasi rectifier |
karo operasi.alarm.lan pratondho fault |
Wektu wiwitan sing alus |
3s-10s |
pengaruh fault rectifier |
Ora mengaruhi paramèter set rectifier nalika rectifier ing fault |
Ngawasi jarak jauh |
Kanthi pangukuran jarak jauh & remot kontrol & fungsi remote signaling. nyedhiyakake standar RS485&Antarmuka TCP/IP lan 6 set port output kontak garing & Baterei Temp.Sensor |
Unit ngawasi |
Basa Inggris ing layar LCD saka rectifier, |
Parameter bisa disetel liwat unit ngawasi. karo set parameter lan daya-gagal fungsi nyimpen data. Maks 1000 Unit ventilasi. |
Cara instalasi |
Dhukungan modul rectifier swappable |
Remot kontrol |
rectifier miwiti lan nutup.test baterei. equalize lan ngambang daya ,DIN / DO konfigurasi lan ing |
Fungsi weker |
Kanthi AC liwat voltase / ing voltase.DC voltase liwat / under.modul Komunikasi fault lan liwat weker suhu,Baterei nyopot,Surge lan liya-liyane |
5 |
Safety |
Resistance insulasi |
Tes voltase 500VDC, Resistance Isolasi ≥10M (tekanan atmosfer normal, suhu normal, asor relatif <90%, ora kondensasi) |
Kekuwatan insulasi |
Input menyang output: 3500VDC @1min&bocor saiki ≤10mA |
Input kanggo enclosures: 3500VDC @1min&bocor saiki ≤10mA |
Output kanggo enclosures:750VDC @1min&bocor saiki ≤10mA |
Sistem bocor saiki |
≤3.5mA(220Vac input) |
Syarat kinerja grounding |
Sistem karo lemah operasi lan lemah pangayoman.with cetha tandha.the resistance antarane enclosures distribusi lan kabeh komponen logam palpable lan grounding nut ora luwih saka 0.1Ω |
proteksi kilat AC |
Sisih peralatan AC bisa nanggung simulasi kilat impuls Arus gelombang 8/20μS lan dirating amplitudo 40kA.(Opsional) |
EMC |
Sesuai karo EN55022 KELAS A,GB9254 KELAS A,FCC BAGIAN 15 KELAS A,GB17626-1998,IEC 61000-3-2 |
6 |
Baty |
Weker lan proteksi voltase sithik baterei (BLVD) |
Nalika voltase DC ngisor Nilai batesan pangayoman baterei lan ora ana input AC. weker proteksi baterei.tahan kanggo 1 min.proteksi baterei DC nyambung Cut mati. |
Fungsi manajemen baterei |
Kanthi fungsi manajemen baterei; kanthi fungsi ngalih manual utawa otomatis status pangisian daya equalized utawa float saka baterei.; Kompensasi suhu kanggo voltase output sistem,(voltase equalized lan ngambang bisa diatur kanthi otomatis adhedhasar 1 ~ 2 00 (luwes) mV / sel / ℃. sing luwih dhuwur suhu baterei.). |